Lies die bedienungsanleitung für Andrews PAC22 Series 2 (3 Seiten) kostenlos online; sie gehört zur Kategorie Klimaanlage. Dieses Handbuch wurde von 45 Personen als hilfreich bewertet und erhielt im Schnitt 4.9 Sterne aus 23 Bewertungen. Hast du eine Frage zu Andrews PAC22 Series 2 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/3

Clickwww.andrews-sykes.com
or Call Us Free 0800 211 611
PAC22 Series 2
Portable Air Conditioning
Operating Instructions
& Safety Guide
General Safety
Keep children and animals away from air conditioning units.
Never leave them alone in a room where the units in use.
This equipment should only be used by a competent person who
has read and understood these instructions.
Never operate this equipment if you are ill, feeling tired or under the
influence of alcohol or drugs.
Keep the Air Conditioning vents clear of all obstructions.
Never put anything on top of the unit or block the air outlets.
Make sure equipment is switched off and unplugged after use.
Never leave switched on or unattended.
Do not use the unit where sunlight is shining directly onto it.
Check condition of equipment before use. If unit is showing signs
of damage contact your supplier immediately.
Electrical Safety
This unit requires a 230 volt electrical supply. It plugs into a standard BS1363
domestic socket.
Always inspect plugs and leads for damage before plugging into the supply -
DO NOT USE IF ANY DAMAGE IS FOUND
Ensure cables are run as not to cause a hazard.
If an extension lead is used, ensure it is of the correct standard , and fully
uncoiled when being used.
Do not lay electrical cables in wet / damp areas.
Do not move equipment whilst operating.
Do not pull equipment by its cable.
It is recommended that electrical equipment is used via a suitable RCD.
Machine not working?
ONLY A COMPETENT ELECTRICIAN SHOULD ATTEMPT TO RECTIFY
ELECTRICAL SUPPLY PROBLEMS. DO NOT REMOVE ANY PANELS FROM THE
MACHINE.
SERIES 2
ProblemLikely CauseSolution
No air flow from the
room unit
Red ‘MAINS’ light offTurn on electricity and/or check mains
supply fuse
No air flow from the
room unit
Red ‘MAINS’ light on.
White ‘DEFROST’
light on
Machine is in defrost mode, do not
adjust anything, machine will revert to
normal run after 10 mins
Insufficient air flow
from the room unit
Blocked air filterClean filter
No coolingGreen ‘COOLING’
light off
Revolve thermostat knob fully anti-
clockwise to ‘1’. Wait 10 minutes for
time delay on start-up.
No coolingAmber ‘ATTENTION’
light illuminated. High
pressure trip.
Press ‘+’ button to re-set and check for:
Lack of water flow... kinked hoses?
Shortage of water..... top up.
External heat exchanger unit mounted in
very high temperature?
Water frozen? Add glycol (33%)
External heat exchanger coil blocked
with dirt.... clean
Air cooled units.... lack of air flow from
exhaust.... kinked or blocked duct, duct
too long.
No coolingAmber ‘ATTENTION’
light illuminated. Low
pressure trip.
Press ‘-’ button to re-set and check for:
No air flow, blocked filter?
Evaporator blocked with ice. Very low air
temperature?
No coolingAmber ‘ATTENTION’
light illuminated. High
level condensate trip.
Condensate pump not reducing water
level. Kink in condensate tube between
room unit and external heat exchanger?
Leak inside room unit. Pump filter inside
room unit blocked. Condensate tube frozen
Produktspezifikationen
| Marke: | Andrews |
| Kategorie: | Klimaanlage |
| Modell: | PAC22 Series 2 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Andrews PAC22 Series 2 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Klimaanlage Andrews
7 Juli 2024
7 Juli 2024
4 Juli 2024
3 Juli 2024
3 Juli 2024
3 Juli 2024
3 Juli 2024
2 Juli 2024
2 Juli 2024
2 Juli 2024
Bedienungsanleitung Klimaanlage
Neueste Bedienungsanleitung für -Kategorien-
20 Januar 2026
20 Januar 2026
19 Januar 2026
19 Januar 2026
17 Januar 2026
14 Januar 2026
14 Januar 2026
13 Januar 2026
12 Januar 2026
12 Januar 2026