APC Back- 750VA Bedienungsanleitung


Seiten 8 Engels UPS

Lies die Bedienungsanleitung für APC Back- 750VA kostenlos online oder lade das PDF herunter. 64 Personen fanden diese Anleitung hilfreich. Frage zu diesem Modell? Stelle eine Frage

Installation and Operation
Back-UPS® BE750G Series
Safety
Specifications
This unit is intended for indoor use only.
Do not operate this unit in direct sunlight, in contact with fluids, or where there
is excessive dust or humidity.
Connect the Back-UPS power cord directly to a wall outlet. Do not use a surge
protector or an extension cord.
Input
Voltage120 VacNominal
Frequency50 Hz/60 Hz auto sensing
Brownout Transfers92 Vrms Typical
Over-voltage Transfer139 Vrms Typical
Output
UPS Capacity
(5 battery backup outlets)750 VA, 450 W
Total Amperage (all outlets)12 A (including UPS output)
Voltage - On Battery115 Vrms ± 8% step approximated sine wave
Frequency - On Battery50 Hz/60 Hz ± 1 Hz
Transfer Time6 ms Typical, 10 ms maximum
Protection and
Filtering
AC Surge ProtectionFull time, 354 Joules
Phone/DSL/FAX surge protectionSingle line (2 wire)
Cable/CAT V/DSS surge protectionOne coax input/output
Network surge protection10/100 Base -T ethernet
EMI/RFI FilterFull time
AC InputResettable circuit breaker
Battery
TypeSealed, maintenance-free, lead acid
Replacement battery cartridge RBC17
Average Life3 - 5 years depending on the number of discharge cycles and
environmental temperature
Physical
Net Weight11 lb (5 kg)
Dimensions
Length x Width x Height14 in x 7 in x 4 in
36 cm x 18 cm x 9 cm
Operating Temperature32º F to 104º F (0º C to 40º C)
Storage Temperature5º F to 113º F (–15º C to 45º C)
Operating Relative Humidity0 to 95% non-condensing humidity
Operating Elevation0 to 10,000 ft (0 to 3000 m)
EMC
Compliance
This device complies with part 68 and part 15 of the FCC rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) This device must accept any
interference received, including interference that may cause undesired operation.