Lies die bedienungsanleitung für Carrier 06N (6 Seiten) kostenlos online; sie gehört zur Kategorie Kompressor. Dieses Handbuch wurde von 15 Personen als hilfreich bewertet und erhielt im Schnitt 4.6 Sterne aus 8 Bewertungen. Hast du eine Frage zu Carrier 06N oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/6

Installation Instructions
06N Screw Compressors
Part No. 1TB1047 1 REV C
SAFETY
Failure to follow these instructions could result in
equipment damage, serious personal injury, or death.
• WARNING: ELECTRIC SHOCK HAZARD! Do not operate
compressor or provide electric power to it unless the
compressor terminal box is installed and the terminal box
cover is in place and secured.
•
WARNING: Do not provide power to unit or turn-on compressor
unless suction and discharge service valves are open.
•
WARNING: ELECTRIC SHOCK HAZARD! Do not remove the
compressor terminal box cover until all electrical sources
have been disconnected.
•
WARNING: CONTENTS UNDER PRESSURE! Compressor
contains oil and refrigerant under pressure. Pressure
must be relieved before installation, servicing or opening
any connections.
•
WARNING: RISK OF PERSONAL INJURY! HOT and COLD
surface temperatures can occur during operation and can
result in severe burns or frostbite.
•
WARNING: RISK OF PERSONAL INJURY! Only approved
refrigerants and refrigeration oils may be used.
•
WARNING: Use nitrogen or inert gas for tightness/pressure testing.
DO NOT USE oxygen or other industrial gases.
• WARNING: System strength/tightness test pressure may not exceed
the compressor maximum Proof Test pressure on the
tag. Close shutoff valves to isolate compressor if
necessary.
• WARNING: Charge only with refrigerant that conforms to AHRI
Standard 700.
• Only qualified, authorized, and appropriately trained HVAC or
refrigeration personnel, should install, commission, and maintain
this equipment.
• Use appropriate personal safety equipment where required.
Safety goggles, gloves, protective clothing, safety boots, and
hard hats should be worn where necessary.
Safety Decals
Install label 2TB0713 on inside of terminal box cover. Install label
06DA502503 on outside of terminal box cover. Install one label
06DA508142 on outside of terminal box and the other label 06DA508142
on inside of terminal box.
Operating Limits
Maximum Proof Test Pressure: 450 psig
Refer to Figures 1 and 2
Figure 1 –Operating Envelope for Air Cooled Condensing
Figure 2 –Operating Envelope for Water Cooled Condensing
Application Drawings
Refer to Application Drawing 0TB0410
Approved Refrigerants
The 06N screw compressor is specifically designed for use in R-134a
systems.
Approved Lubricants
The following lubricants are approved for use with 06N Series screw
compressors:
• Carrier Material Spec PP47-13, PP47-14, PP47-32, or PP47-34,
Viscosity Grade ISO 220
Note that all POE oils are very hygroscopic (will readily pick up and retain
moisture from the air). Damaging acids can form if moisture is present. Oil
should only be used from a properly sealed container.
Electrical Connections
• Compressor user must provide properly sized motor over-current
protection. Use the electrical data on drawing 0TB0659 or the
compressor nameplate to size the contactor and overload relay or circuit
breaker.
• When circuit breakers are used for motor protection, they must be
permanently marked "Special Purpose - Not For General Use" and
should indicate must trip current not exceeding 140% of compressor
rated load current.
• Motor protection system must protect against primary single-phase
failure.
• Motor over-current protection system must protect all three phases.
• An appropriate terminal box must be installed.
WARNING: Terminal box must be in place, with its cover installed,
before power can be applied.
• Connect the compressor in accordance with the Application Drawing
and the wiring diagram located on the terminal box lid.
• Power wires are to be connected to the terminal pins using ring
terminals and jam nuts.
• The compressor terminals are copper feed through pins. Torque nuts in
accordance with the Application Drawing
•
WARNING: Disturbing the factory installed nut will jeopardize the
seal integrity of the terminal pin.
• The motor temperature thermistors and a separate grounding lug
connection are located in the terminal pin area.
• The T-series compressors are approved for use with Across the Line
and Open or Closed Transition Wye-Delta starting methods.
There are two critical timing parameters associated with the open
transition Wye-Delta starting method.
Duration of the Wye connection shall be 5 to 10 seconds.
WARNING: Overheating of the motor can occur if duration is
too long.
10
20
30
40
50
60
70
80
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Saturated Discharge Temperature (
°C)
Saturated Suction Temperature (°C)
Air Cooled Condensing Discharge Temp. Limit for Full Load
Discharge Temp. Limit for 2/3 Load Discharge Temp. Limit for 1/3 Load
10
20
30
40
50
60
70
80
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Saturated Discharge Temperature (°C)
Saturated Suction Temperature (°C)
Water Cooled Condensing Discharge Temp. Limit for Full Load
Discharge Temp. Limit for 2/3 Load Discharge Temp. Limit for 1/3 Load
Produktspezifikationen
| Marke: | Carrier |
| Kategorie: | Kompressor |
| Modell: | 06N |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Carrier 06N benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Kompressor Carrier
9 September 2025
8 September 2025
19 Juli 2025
19 Juli 2025
19 Juli 2025
Bedienungsanleitung Kompressor
- Fuxtec
- Powerplus
- Verto
- Hitachi
- Bavaria
- Sun Joe
- Oricom
- Dometic
- Pro-Lift
- Laica
- Toolson
- Pansam
- Truper
- Contimac
- Topcraft
Neueste Bedienungsanleitung für -Kategorien-
20 Januar 2026
20 Januar 2026
19 Januar 2026
18 Januar 2026
18 Januar 2026
17 Januar 2026
16 Januar 2026
14 Januar 2026
14 Januar 2026
14 Januar 2026