Lies die bedienungsanleitung für Carrier Aquaforce 30XA (140 Seiten) kostenlos online; sie gehört zur Kategorie Klimaanlage. Dieses Handbuch wurde von 37 Personen als hilfreich bewertet und erhielt im Schnitt 4.7 Sterne aus 19 Bewertungen. Hast du eine Frage zu Carrier Aquaforce 30XA oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/140

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300202-01 Printed in U.S.A. Form 30XA-27SI Pg 1 9-21 Replaces: 30XA-26SI
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Place, Mount, and Rig the Unit . . . . . . . . . 2
• PL
ACING UNIT
• MOUNTING UNIT
• RIGGING UNIT (SEE FIG. 27-29)
Step 3 — Make Refrigerant, Cooler Fluid and Drain
Piping Connections . . . . . . . . . . . . . . . . . . . . . . . 88
• 30XA501 UNIT ASSEMBLY
• GENERAL
• FLOODED COOLER UNITS
• DX COOLER UNITS
• PREPARATION FOR YEAR-ROUND OPERATION
Step 4 — Fill the Chilled Water Loop . . . . . . . . . . 108
• WATER SYSTEM CLEANING
• WATER TREATMENT
• SYSTEM PRESSURIZATION
• FILLING THE SYSTEM
• SET WATER FLOW RATE
• PUMP MODIFICATION/TRIMMING
• PUMP VFD
• SENSORLESS CONTROL (CLOSED LOOP), ACTIVE
SETUP 1
• REMOTE SENSOR (CLOSED LOOP), ACTIVE SETUP 2
• REMOTE CONTROLLER (OPEN LOOP), ACTIVE SETUP
3
• FREEZE PROTECTION
• PREPARATION FOR WINTER SHUTDOWN
Step 5 — Make Electrical Connections . . . . . . . . . 113
• POWER SUPPLY
• FIELD POWER CONNECTIONS (SEE FIG. 61)
• POWER WIRING
• FIELD CONTROL POWER CONNECTIONS
• CCN COMMUNICATION BUS WIRING
• NON-CCN COMMUNICATION WIRING
• FIELD CONTROL OPTION WIRING
• DUAL CHILLER LEAVING WATER SENSOR
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . 136
• ENERGY MANAGEMENT MODULE
• REMOTE ENHANCED DISPLAY
• LOW AMBIENT TEMPERATURE OPERATION
• MINIMUM LOAD ACCESSORY
• UNIT SECURITY/PROTECTION ACCESSORIES
• COMMUNICATION ACCESSORIES
• SERVICE OPTIONS
Step 7 — Leak Test Unit . . . . . . . . . . . . . . . . . . . . .136
St
ep 8 — Refrigerant Charging . . . . . . . . . . . . . . . .136
• DEHYDRATION
• REFRIGERANT CHARGE
Step 9 — Optional BACnet Communication Wiring .137
• MS/TP WIRING RECOMMENDATIONS
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazard-
ous due to system pressures, electrical components, and equip-
ment location. Only trained, qualified installers and service me-
chanics should install, start up, and service this equipment.
When working on the equipment, observe precautions in the liter-
ature, and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky equipment.
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles
and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil
that may come out of the lines and as a gage for how
much oil to add to the system.
e. Carefully un-sweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal inju-
ry or death.
WARNING
Electrical shock can cause personal injury and death. Shut off
all power to this equipment during installation. There may be
more than one disconnect switch. Tag all disconnect locations
to alert others not to restore power until work is completed.
AquaForce
®
30XA080-501
Air-Cooled Liquid Chillers
Produktspezifikationen
| Marke: | Carrier |
| Kategorie: | Klimaanlage |
| Modell: | Aquaforce 30XA |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Carrier Aquaforce 30XA benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Klimaanlage Carrier
11 September 2025
10 September 2025
8 September 2025
30 August 2025
30 August 2025
30 August 2025
19 Juli 2025
19 Juli 2025
8 Juli 2025
Bedienungsanleitung Klimaanlage
- Ocean Breeze
- Monzana
- Xiaomi
- Gree
- Moa
- Fronius
- Hotpoint
- NewAir
- Mitsubishi
- Bavaria
- Midea
- MDV
- Melissa
- MPM
- Saunier Duval
Neueste Bedienungsanleitung für -Kategorien-
20 Januar 2026
20 Januar 2026
19 Januar 2026
19 Januar 2026
17 Januar 2026
14 Januar 2026
14 Januar 2026
13 Januar 2026
12 Januar 2026
12 Januar 2026