Lies die bedienungsanleitung für Fantini Cosmi P30A (2 Seiten) kostenlos online; sie gehört zur Kategorie Gasdetektor. Dieses Handbuch wurde von 11 Personen als hilfreich bewertet und erhielt im Schnitt 5.0 Sterne aus 6 Bewertungen. Hast du eine Frage zu Fantini Cosmi P30A oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage

Seite 1/2
INSTALLATION
P30A GENERAL CONTROL PANEL INSTALLATION
Screw the fixing stay-bar and release the control panel
socket . Remove the socket by pulling with a
screwdriver on the latching tabs.
Fix the terminal-holders of the wall detector (according
to the fixing systems shown hereby) in a dry not
dripping place.
SENSORS DETECTORS
They shuold be fixed on a wall at an approximate
distance of 2 meters form the gas device in such a
position as to allow natural air circulation:
-S71 for specific ligth gases (natural gas, city gas) has
to be fixed at an high level approximately 30/40 cm
from the ceiling.
-S72 for heavy gases (cylinder liquid gas LGP) has to
be fixed to a low level approximately 30/40 cm above
the floor.
Avoid installing sensors:
-behind barriers that can prevent the natural air
circulation in the area
-close to air conditiong units (minimum distance 2
meters)
-close to fumes, steams or other exhalation sources
Remove the cover four front retaining screws, fix the
base to the wall, using for the cables entrance the
special press-.cables.
GAS DETECTOR VALVE
Choose the gas interception valve among one of the
serie Z-EV, generally closed with quick on and off
realease switch, class A with approval (or
corresponding models) according to diameter and gas
pipe type.
Install the valve in the most suitable part of the plant
downstream the counter or at the exit of the
accumulation tanks.
ACOUSTIC/VISUAL EXTERNAL SIGNALLER
Use the self-fed type most suitable with your kind of
plant, place it in an easely visibles place.
CONNECTIONS WITH POSSIBLE FIRE ALARM
CONTROL SYSTEM AND/OR ANTI-INTRUSION
DEVICE.
The voltage free terminal exchange contact available
for the external acoustic/visual signaller can in
alternative be used for connections with alredy exiting
central alarm panels.
CONTROL PANEL
CENTRAL CONTROL CONSOLE
Visual indicator: normally switched off, flashes in case
of alarm. It can be switched off only through the reset
button.
Operating indicator: always switched on.
Alarm sensors indicators: generally switched off they
switch on when the connected sensor send an alarm
signal. They switch off when the gas concentration
goes back to the allowed levels.
Test switcher to verify the device except for the
sensors.
Switch for external siren silencing: it allows to switch
off the siren even during an alarm situation.
Reset switch to stop the alarm after the cause has
been removed.
Operation delay: unique for all sensors, regulates the
delay once that a warning situation has been detected
by all sensors and it has activated the general alarm.
Acoustic signaller: positioned inside the central
control panel operates in case of alarm. It can be
switched off only through the reset switch.
SENSOR
Operating indicator: always switched on.
Fault indicator sensor
Alarm indicator: generally switched off, it operates
and remains on for all the time in which the gas
concentration remains above the established level.
A
B
C
D
E
F
G
H
I
L
M
C
B
I
L
M
F
H
G
A
SENSORS
CENTRAL
(INTERNALS)
93
91
110
P30A CENTRAL CONTROL PANEL:
OVERALL DIMENSIONS
WALL FIXING
BACK-CONTROL CONSOLE FIXING
EXTRACTION SOCKET