This modular changeover switch is not a disconnector.
The isolation must be ensured with an appropriate
device. The changeover incoming must be protected
against short circuit with an appropriate MCB 63A - 6kA
- C curve.
NOTE 1: In Australia and NZ, the Main Supply Neutral
upstream of the MEN connection is NOT allowed to be
switched. (AS/NZS 3010).
Specic for Australia
Modular changeover 63A
with centre OFF position
SF263
MAIN SWITCH BOARD
Installation
main switch
*
*
May also be
a circuit breaker
To electrical
installation
L
L
GN
N
GN
GS
Generator SetNormal Supply
Outgoing
Incoming
Main Neutral Link
SF263
Check power
protection
NOTE 2: Refer to AS/NZS 3000, 3010 and
local Service and Installation Rules for specic
requirements.
Alternative supply generator: typical location of manual changeover device with centre "off" position in the main
switch board.
Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com