Hager SF463 Bedienungsanleitung
Seiten 1 Schalter
Lies die Bedienungsanleitung für Hager SF463 kostenlos online oder lade das PDF herunter. Diese Anleitung wurde 6 Mal aufgerufen. Frage zu diesem Modell? Stelle eine Frage

This modular changeover switch is not a disconnector.
The isolation must be ensured with an appropriate
device. The changeover incoming must be protected
against short circuit with an appropriate MCB 63A - 6kA
- C curve.
NOTE 1: In Australia and NZ, the Main Supply Neutral
upstream of the MEN connection is NOT allowed to be
switched. (AS/NZS 3010).
Specic for Australia
z
Modular changeover 63A
with centre OFF position
SF463
R
L1
III
G1W
L2
III
G2B
L3
III
G3N
N
III
GN
L3
L2
L1
N
L2
L3
L1
Generator Set
Normal Supply
MAIN SWITCH BOARD
Outgoing
Incoming
Main Neutral Link
SF463
Installation
main switch
*
*
May also be a
circuit breaker
To electrical
installation
GS
Check power
protection
Alternative supply generator: typical location of manual changeover device with centre "off" position in the main
switch board.
NOTE 2: Refer to AS/NZS 3000, 3010 and
local Service and Installation Rules for specic
requirements.
Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com
OCOM 129414Hager 09.176S5503d