Lies die bedienungsanleitung für Hager ST301 (1 Seiten) kostenlos online; sie gehört zur Kategorie Nicht kategorisiert. Dieses Handbuch wurde von 24 Personen als hilfreich bewertet und erhielt im Schnitt 4.5 Sterne aus 3 Bewertungen. Hast du eine Frage zu Hager ST301 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage

Seite 1/1
5.50 General Catalogue • Modular Devices • Technical
Transformers
Safety Transformers
These transformers are designed to ensure personal safety, their
primary winding are electrically separated from their secondary
windings and they are intended to feed separated extra low voltage
circuits U 50V. A thermal overload, in the primary windings, ensures
that if a short circuit or an overload occurs in the output it will not
damage the device.
Bell Transformers
Bell transformers are similar to safety transformers but the
secondary voltages do not exceed 24 volts, they are also similarly
protected against short circuits and overloads, by thermal protection
in the primary winding.
Compliance with the Standards
The bell and safety transformers conform with BS EN 61558.
Where transformers are to be used in a common enclosure with other
devices heat dissipation inserts LZ060 should be used.
Recommendation of Use
• To link only one secondary (never link both simultaneously)
• Do not connect (in series or in parallel) secondaries of different
transformers
24 V230 V
U1
U2
U3
Technical Specification
ST301 ST303 ST305 ST312 ST313 ST314 ST315
Nominal Power4VA8VA16VA 25VA 16VA 40VA 63VA
Designation BellBellBellSafety Safety Safety Safety
Primary Voltage230 Volts230 Volts230 Volts230 Volts230 Volts230 Volts230 Volts
Secondary VoltageU28 Volts8 Volts8 Volts12 Volts12 Volts12 Volts12 Volts
In = 0.5AIn =1AIn = 2AIn = 2.08AIn = 1.33AIn = 3.33AIn = 5.25A
U312 Volts12 Volts12 Volts24 Volts24 Volts24 Volts24 Volts
In = 0.33AIn = 0.67AIn = 1.33AIn = 1.04AIn = 0.67AIn = 1.67AIn = 2.63A
No Load U212 Volts15 Volts12 Volts14 Volts16 Volts14 Volts14 Volts
Secondary Voltage U318 Volts22 Volts19 Volts29 Volts30 Volts27Volts27 Volts
Galvanic Insulation4kV 4kV4kV4kV 4kV4kV 4kV
Max Functional Temperature35ºC 35ºC 35ºC 35ºC 35ºC 35ºC 35ºC
Overload and S/C ProtectionThermal cut out in the primary winding
Insulation ClassHHBBBBH