Lies die bedienungsanleitung für Hubbell J67T (40 Seiten) kostenlos online; sie gehört zur Kategorie Heizung. Dieses Handbuch wurde von 4 Personen als hilfreich bewertet und erhielt im Schnitt 4.9 Sterne aus 2.5 Bewertungen. Hast du eine Frage zu Hubbell J67T oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage

Seite 1/40
1
OPERATING AND MAINTENANCE
MANUAL FOR
ELECTRIC BOOSTER HEATER
ELECTRIC HEATER COMPANY
BASE MODEL “ J ”
UM ANSI/NSF5
2017 Edition
2
HUBBELL
ELECTRIC HEATER COMPANY
45 SEYMOUR STREET
P.O. BOX 288
STRATFORD, CT 06615
PHONE: (203) 378-2659
FAX: (203) 378-3593
INTERNET: http://www.hubbellheaters.com
-- IMPORTANT --
Alw
ays reference the full model number and serial number when calling the factory.
WARNING / CAUTION
1. Tank is to be completely filled with water and all air is to
be vented before energizing.
2. Due to the rigors of transportation, all connections should be checked for tightness before
heater is placed in operation.
3. Safety relief valve must be installed in tapping provided.
4.
The
refractory material used in heating elem
ents may absorb some mo
isture during
transit, periods of storage, or when subjected to a humid environment. This moisture
absorption results in a cold insulation resistance of less than one (1) megohms. If this
heater has been subjected to the above condition, each heating element must be checked
for insulation resistance before energizing. Contact the factory for a replacement element.
5. KEEP AWAY FROM LIVE ELECTRICAL CIRCUITS.
Do not perform any maintenance, make any adjustments, or replace any components
inside the control panel with the high voltage power supply turned on. Under certain
circum
stances, dangerous potentials may exist
even when the power supply is off. To
avoid casualties, always turn the power supply safety switch to off, turn the charge or
ground the circuit before performing any maintenance or adjustment procedure.
6. The unit is designed to operate at pressure not more than 150 psi.
7. Generalized instructions and procedures cannot anticipate all situations. For this reason,
only qualified installers should perform
the in
stallations. A qualified installer is a person
who has licensed training and a working knowledge of the applicable codes, tools,
equipment, and methods necessary for safe installation of an electric resistance water
heater. If questions regarding installation arise, check your local plumbing and electrical
inspectors for proper procedures and codes. If you cannot obtain the required
information, contact the company.
8. Water Quality Requirements – Recommended water hardness is 4 to 6 grains of
hardness per gallon (GPG). Water hardness above 6 GPG should be treated by a water
conditioner (water softener or in-line treatment). Water hardness below 4 GPG also
requires treatment to reduce potential corrosion. Excessive GPG will result in higher
operating and m
aintenance costs and will reduce product longevity. Chlorides mu
st
not exceed 50 parts per million (ppm). Excessive chlorides will result in metallic
corrosion and will reduce product longevity. Water treatment has been shown to
reduce costs associated with de-liming the booster as well as reducing metallic
corrosion. Product failure caused by these conditions is not covered under warranty.
See warranty for com
p
lete details.
9. This water heater is not intended for space heating applications.
10. The water heater is factory set at 185°F for booster water heating applications. This
results in the possibility of a scalding water injury. A full thickness skin burn can
occur in less than one second of exposure to water at this temperature.