IFM OGE301 Bedienungsanleitung


Lies die bedienungsanleitung für IFM OGE301 (4 Seiten) kostenlos online; sie gehört zur Kategorie Nicht kategorisiert. Dieses Handbuch wurde von 10 Personen als hilfreich bewertet und erhielt im Schnitt 4.6 Sterne aus 5.5 Bewertungen. Hast du eine Frage zu IFM OGE301 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage

Seite 1/4
Operating instructions
Through-beam sensor
OGE3xx / OGS3xx
UK
UK
UK
UKUK
UK
704461 / 01 01 / 2009
2
1 Preliminary note
1.1 Symbols used
Instruction
> Reaction, result
Cross-reference
Important note
Non-compliance can result in malfunctions or interference.
2 Functions and features
The through-beam sensor detects objects and materials without contact and
indicates their presence by a switching signal.
Range: ( type label).
3 Installation
1 1
LED1:
Install the receiver (OGE3xx) and secure it to a bracket.
Align the transmitter (OGS3xx) to the receiver and secure it in the same way.
Maximum range only with accurate alignment.
4 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electri-
cal equipment must be adhered to.
Ensure voltage supply to EN 50178.
Disconnect power.
Connect the unit as follows:
3
UK
Transmitter (OGS3xx) connector
1
3
L+
L
pin 1 = L+
(pin 2: not connected)
pin 3 = L-
(pin 4: not connected)
Transmitter (OGS3xx) cable *
L+
L
BN
BU
BN = L+
BU = L-
Receiver (OGE3xx) connector
L+
L
1
4
3
pin 1 = L+
(pin 2 = not connected)
pin 3 = L-
pin 4 = load
Receiver (OGE3xx) cable *
BN
BK
BU
L+
L
BN = L+
BU = L-
BK = load
* Core colours: BN = brown, BU = blue, BK = black
5 Operation
Check whether the unit operates correctly.
Transmitter (OGS3xx): The green LED is lit when the sensor is ready for
operation.
Receiver:
Dark-on switching units (OGE-DPKG): the output is switched / the yellow LED
is lit when an object is detected.
Light-on switching units (OGE-HPKG): the output is switched / the yellow LED
is lit when no object is detected.