Samsung AM080FXVAGH Bedienungsanleitung

Samsung Klimaanlage AM080FXVAGH

Lesen Sie kostenlos die šŸ“– deutsche Bedienungsanleitung für Samsung AM080FXVAGH (110 Seiten) in der Kategorie Klimaanlage. Dieser Bedienungsanleitung war für 37 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/110
DVM S
AM FXVAGR Series✓✓✓
AM FXVAGH Series✓✓✓
AM HXVAGH Series✓✓✓
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
2
Contents
Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Preparing for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Selecting installation location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Space requirement for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Base construction and installation of the outdoor unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installing the wind/snow prevention duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Refrigerant pipe installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Electrical wiring work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Air tightness test and vacuum drying. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Pipe insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Charging refrigerant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Basic segment display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Setting outdoor unit option switch and key function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Setting the MCU and Pipe Addresses (for HR Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Things to check after completing the installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
Inspection and test operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101
Inspection and trial operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103
Automatic refrigerant amount detection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
(Applicable in countries with separate collection systems)
This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g.
charger, headset, USB cable) should not be disposed of with other household waste at the end of their working life.
To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate
these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material
resources.
Household users should contact either the retailer where they purchased this product, or their local government
office, for details of where and how they can take these items for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This
product and its electronic accessories should not be mixed with other commercial wastes for disposal.
For information on Samsung’s environmental commitments and product-specific regulatory obligations, e.g.
REACH, WEEE, Batteries, visit : samsung.com/uk/aboutsamsung/samsungelectronics/corporatecitizenship/data_
corner.html
3
ENGLISH
Safety precautions
Please follow the following safety information for safety of the installer and the user.
ā‡ DVM S air conditioner uses R-410A refrigerant.
t When using R-410A, moisture or foreign substances may affect the performance and reliability of the
product. Safety precautions must be obeyed when installing the refrigerant pipe.
t The designed maximum pressure of the system is 4.1MPa and therefore select appropriate material and
thickness according to the regulations.
t R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when filling the
refrigerant. (If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product
malfunction.)
ā‡ You must connect the indoor units for R-410A refrigerant. Refer to product catalog to find out the models
names for connectable indoor units. (If you connect the indoor units that are not designed for R-410A, it
cannot operated normally.)
ā‡ After completing the installation and trial operation, explain to the user how to use and maintain the product. Also,
hand over this installation manual so that it can be stored by the user.
ā‡ Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible for
any installation related claims from the user occurred by neglecting warnings and cautions stated in this manual.
(Installer will be responsible for any service charges that may occur)
ā‡ Generally, system air conditioners should not be relocated after installation. But when it has to be relocated for
inevitable reasons, please contact Samsung’s qualified dealers for system air conditioners.
WARNING t Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION
t Hazards or unsafe practices that may result in minor personal injury (to installer/user) or
property damage.
SEVERE WARNING SIGNS
Consult qualified installer or dealer for installation.
ī€ƒX When installation is done by unqualified person, problems such as water leakage, electric shock or fire may occur.
Installation work must be done properly according to this installation manual.
ī€ƒX When installation is not done properly, it may cause water leakage, electric shock or fire.
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding
allowable safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before the
installation.
ī€ƒX When refrigerant leaks and exceed dangerous concentration level, it may cause suffocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may occur and
it may cause injury.
Use the supplied accessories, specified components and tools for the installation.
ī€ƒX Do not use the pipe and the installation product used for the R-22 refrigerant.
ī€ƒX Failure to use the specified components can cause product fall down, water leakage, electrical shock, and fire. (The
pipe and flare components used for R-22 refrigerant must not be used)
Install the outdoor unit on a hard and even place that can support its weight.
ī€ƒX If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.


Produktspezifikationen

Marke: Samsung
Kategorie: Klimaanlage
Modell: AM080FXVAGH
Produktfarbe: Weiß
AC Eingangsspannung: 380 - 415 V
AC Eingangsfrequenz: 50 Hz
Typ: Klimaanlageneinheit Außen
KƤltemittelart: R410A
Kühlmittelgewicht: 5500 g
Invertertechnologie: Ja
Klimaanlage Funktionen: Cooling, Fan, Heating
Kühlkapazität in Watt (nominal): 22400 W
Heizleistung in Watt (max): 25200 W
Energieverbrauch pro Stunde (Kühlung): - kWh
Energieverbrauch pro Stunde (Heizung): - kWh
Jährlicher Energieverbrauch (Kühlung): - kWh
Heizleistung in Watt (nominal) (wƤrmere Heizperiode): - W
Heizleistung in Watt (nominal) (durchschnittliche Heizperiode): - W
Heizleistung in Watt (nominal) (kƤltere Heizperiode): - W
SchlauchlƤnge (max.): 200 m
Betriebstemperaturbereich (Kühlung) (T-T): -5 - 48 °C
Betriebstemperaturbereich (Heizung) (T-T): -20 - 24 °C
JƤhrlicher Energieverbrauch (Heizung) (wƤrmere Heizperiode): - kWh
JƤhrlicher Energieverbrauch (Heizung) (durchschnittliche Heizperiode): - kWh
JƤhrlicher Energieverbrauch (Heizung) (kƤltere Heizperiode): - kWh
zulässige Last (Kühlung): - kW
zulƤssige Last (Heizung) (wƤrmere Heizperiode): - kW
zulƤssige Last (Heizung) (durchschnittliche Heizperiode): - kW
zulƤssige Last (Heizung) (kƤltere Heizperiode): - kW
GerƤuschpegel InnengerƤt (hohe Geschwindigkeit): - dB
Geräuschpegel Außengerät: 57 dB
Kühlender Luftstrom (outdoor unit): 173 m³/h
Menge Außengeräte: 1
Breite der Outdooreinheit: 880 mm
Tiefe der Outdooreinheit: 765 mm
Hƶhe der Outdooreinheit: 1695 mm
Außengerätsgewicht: 190000 g
Gasleitungsdurchmesser: 19.05 mm
Durchmesser Flüssigkeitsschlauch: 9.52 mm
Strom (Kühlung): 8 A
Kühlung Energieeffizienz: 4.48
Heizung Energieeffizienz: 4.94
Strom (Heizung): 8.2 A
Energieverbrauch (Kühlen) (max): 5000 W
Energieverbrauch (Heizung) (max): 5100 W
Kompressorentyp: Doppeldrehelement
Außengerät Schallleistungspegel: 77 dB
Kühlleistung (nominal): 76400 BTU/h
Heizleistung (nominal): 86000 BTU/h