Seaward AGL-5 Bedienungsanleitung
Lies die bedienungsanleitung für Seaward AGL-5 (2 Seiten) kostenlos online; sie gehört zur Kategorie Detektor. Dieses Handbuch wurde von 5 Personen als hilfreich bewertet und erhielt im Schnitt 4.5 Sterne aus 3 Bewertungen. Hast du eine Frage zu Seaward AGL-5 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/2

AGL-5
Airfield Ground
Lighting Tester
Operating Instructions
Bracken Hill
South West Industrial Estate
Peterlee
Co Durham
SR8 2SW
ENGLAND
Tel: +44(0)191 5863511
www.seaward.co.uk
sales@seaward.co.uk
service@seaward.co.uk
Part Number 374AA550 Revision 1
© 2009 Seaward Electronic Ltd
Limited Warranty & Limitation of Liability
SEAWARD Electronic Limited guarantees this product to be free
from defects in material and workmanship under normal use and
service for a period of 1 year. The period of warranty will be
effective at the day of delivery.
(c) Copyright 2009
All rights reserved. Nothing from this edition may be multiplied, or
made public in any form or manner, either electronically,
mechanically, by photocopying, recording, or in any manner,
without prior written consent from SEAWARD Electronic Limited.
This also applies to accompanying drawings and diagrams.
Due to a policy of continuous development SEAWARD Electronic
Limited reserves the right to alter the equipment specification and
description outlined in this publication without prior notice and no
part of this publication shall be deemed to be part of any contract
for the equipment unless specifically referred to as an inclusion
within such contract.
DECLARATION OF CONFORMITY
As the manufacturer of the apparatus listed, declare under our sole
responsibility that the product:
AGL-5 Airfield Ground Lighting Tester
To which this declaration relates are in conformity with the relevant
clauses of the following standard:
BS EN 61243-2:1998
BS EN 61243-3:1999
BS EN 61326:1998
Electrical equipment for measurement, control and laboratory
user-EMC Requirements
Performance: The instrument operates within specification
when used under the conditions in the above
standards EMC and Safety Standards.
The product identified above conforms to the requirements of
Council Directive 89/336/EEC and 73/23 EEC.
Seaward Electronic Ltd is registered under BS EN ISO9001:2000
Certificate No: Q05356.
1 Important Information
These operating instructions are intended for the use
of adequately trained personnel.
Before use, ensure that the AGL-5 tester is clean and
dry; visually inspect all parts. Any damage must be
rectified prior to use.
Never hold an AGL-5 Tester between the hand-
guard and the contact electrode.
Always prove the AGL-5 Tester before AND after
use.
1. Holding the AGL-5 tester by the handles,
behind the handguards, connect the
instrument to a Seaward PH3-LLT proving
unit and verify that the LED indicators are
illuminated.
2. Holding the AGL-5 tester by the handles,
behind the handguards, place the contact
electrodes in contact with the circuit
under test.
3. If the LED indicators are illuminated there
is a voltage greater than the threshold
voltage present at the probe tips.
4. If the LED indicators do not illuminate any
voltage present at the probe tips is less
than the threshold voltage.
5. Repeat step 1 above to verify that the
instrument is still operational.

2 Proving
• Connect the one probe to the BLACK
terminal.
• Connect the other probe to the RED terminal.
• Press the probe down onto the RED terminal
as shown below to operate the internal
micro-switch.
• Confirm that the neon illuminates indicating
the test voltage is active.
• Confirm that the LED indicators in the AGL-5
illuminate.
• Disconnect both probes from the proving
unit.
3 Specifications
Maximum Working
Voltage
5000V AC/DC
Threshold voltage 50V AC / 70V DC
Operating Current
<3.5mA AC/DC at max
working voltage
Indicator
High intensity LED with
polarizing filter
Handle length 160mm
Overall Length 530mm
Probe tip length 38mm
Hand guard height
>10mm over 70%
circumference
Length of insulation
between contact
electrode and hand-
guard
574mm
Un-insulated contact
electrode length
5mm
Contact Electrode
diameter
3mm
Lead length between
probes
0.8m triple insulated cable
Construction
High Impact, total
encapsulation
Compliance
BS EN 61243-2:1998
4 Maintenance
Clean only with a dry cloth; do not use solvents.
Before use, ensure unit is clean and dry; visually
inspect test terminals and case. Any damage must be
rectified to preserve user safety.
5 Service and Calibration
To maintain the specified performance, the
instrument must be verified at regular intervals by
either the manufacturer or an authorised Seaward
Service Agent. We recommend a calibration period
of one year.
For help or advice on Service and Calibration
contact:
Service Department
Seaward Electronic
Bracken Hill
South West Industrial Estate
Peterlee
Co Durham SR8 2SW
England
Tel: 0191 5878739 / 0191 5878737
Email: service@seaward.co.uk
Web: www.seaward.co.uk
Produktspezifikationen
Marke: | Seaward |
Kategorie: | Detektor |
Modell: | AGL-5 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Seaward AGL-5 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Detektor Seaward
3 September 2025
Bedienungsanleitung Detektor
- Uniden
- Satel
- Hager
- Gamma Scout
- Kemo
- Joy-it
- Nexa
- B/R/K
- Black And Decker
- S.E. International
- Vimar
- Inovonics
- Rocky Mountain
- PCE Instruments
- Guardian Avionics
Neueste Bedienungsanleitung für -Kategorien-
4 September 2025
4 September 2025
4 September 2025
4 September 2025
3 September 2025
3 September 2025
3 September 2025
3 September 2025
1 September 2025
30 August 2025