Carrier NSA-OA-RH Bedienungsanleitung

Carrier Messung NSA-OA-RH

Lies die bedienungsanleitung für Carrier NSA-OA-RH (9 Seiten) kostenlos online; sie gehört zur Kategorie Messung. Dieses Handbuch wurde von 24 Personen als hilfreich bewertet und erhielt im Schnitt 4.8 Sterne aus 12.5 Bewertungen. Hast du eine Frage zu Carrier NSA-OA-RH oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage

Seite 1/9
RH Outside Air Thermistor
Installation and Operation
#NSA-HH/RH2-CP-O-C, NSA-HH/RH3-CP-O-C 11/14/2019
Specifications subject to change without notice.
Catalog No. 11-808-776-01 Page 1 of 9
Overview
The Carrier Relative Humidity with Thermistor Outside Air Series utilizes a thermoset
polymer capacitive sensing element with factory applied hygroscopic filter to deliver a
proportional analog current or voltage output signal. The hygroscopic filter provides added
resistance to moisture, dust, and other chemicals for greater long term reliability. The RH
Outside Air transmitter features integral DIP switches for field selection of the proper output
signal and supply voltage to meet your applications requirements. Each unit also contains
0%, 50%, and 100% test options to verify that the transmitter is both working and wired
properly. Field calibration also can be performed by using the increment and decrement
calibration DIP switches without the need to replace the sensing element. These
enhancements provide increased flexibility and outstanding long-term reliability. Outside Air
configurations feature a weatherproof Euro style enclosure with gasketed cover and
conformally coated circuit boards for added moisture and chemical resistance.
Applications: Monitor Outdoor Air Humidity, Economizer Control, Psychrometric
calculations such as Enthalpy and Dew point, Wash down Applications
Part Numbers
NSA-HH/RH2-CP-O-C NSA-HH/RH3-CP-O-C
Specifications
RH Supply Voltage
(Reverse Polarity Protected):
4-20 mA: 250 Ohm Load: 15 - 40 VDC / 18 - 28 VAC
500 Ohm Load: 18 - 40 VDC / 18 - 28 VAC
0-5 VDC: 12 - 40 VDC / 18 - 28 VAC | 0-10 VDC: 18 - 40 VDC / 18 - 28 VAC
RH Supply Current (VA):
Voltage Output: 8 mA max (0.32 VA) | Current Output: 24 mA max (0.83 VA)
RH Output Load Resistance:
4-20 mA: 700 Ohms max | 0-5 VDC or 0-10 VDC: 4K Ohms min
RH Output Signal:
2-wire: 4 - 20 mA (default) | 3-wire: 0-5 or 0-10 VDC and 4 - 20 mA (Field Selectable)
RH Accuracy @ 77°F (25°C):
+/- 1% over 20% RH Range between 20 to 90% | +/- 2%, 3%, or 5% from 10 to 95%
RH Measurement Range
0-100%
Operating RH Range:
0 to 95% RH, non-condensing (Conformally Coated PCB’s)
Operating Temperature Range:
-40 to 140°F (-40 to 60°C)
Storage Temperature Range:
-40 to 149°F (-40 to 65°C)
RH Stability | Repeatability | Sensitivity:
Less than 2% drift / 5 years | 0.5% RH | 0.1% RH
RH Response Time (T63):
20 Seconds Typical
RH Sensor Type:
Capacitive with Hydrophobic Filter
RH Transmitter Stabilization Time:
30 Minutes (Recommended time before doing accuracy verification)
RH Connections | Wire Size:
Screw Terminal Blocks (Polarity Sensitive) | 16 (1.31 mm²) to 26 AWG (0.129 mm²)
RH Terminal Block Torque Rating:
4.43 to 5.31 lb-in (0.5 to 0.6 Nm)
RH NIST Test Points:
Default Test Points: 3 Pts (20%, 50% & 80%) or 5 Pts (20%, 35%, 50%, 65% & 80%)
1% NIST Test Points: 5 Pts within selected 20% Range (ie. 30%-50% are 30, 35, 40,
45 & 50)
Nominal Thermistor Resistive Output @
77°F (25°C) (Lead Wire Colors):
10KΩ- (White/Green)
Thermistor Accuracy 32-158°F (0-70°C):
+/- 0.36°F (0.2°C)
Thermistor Power Dissipation Constant:
3 mW/°C
Thermistor Sensor Response Time
(T63):
10 Seconds nominal
Lead Wire Length | Conductor Size:
14” (35.6 cm) | 22 AWG (0.65 mm)
Insulation | Rating:
Etched Teflon (PTFE) Colored Leads | Mil Spec 16878/4 Type E
Enclosure Specifications (Material,
Flammability, Temperature, NEMA/IP
-EH” Enclosure: ABS Plastic; UL94-V0; -40 to 140°F (-40 to 60°C)
-4X” Enclosure: Polystyrene Plastic; UL94-V2; -40 to 158°F (-40 to 70°C); NEMA 4X


Produktspezifikationen

Marke: Carrier
Kategorie: Messung
Modell: NSA-OA-RH

Brauchst du Hilfe?

Wenn Sie Hilfe mit Carrier NSA-OA-RH benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten