Lies die bedienungsanleitung für Carrier NSA-RH-ROOM (9 Seiten) kostenlos online; sie gehört zur Kategorie Messung. Dieses Handbuch wurde von 59 Personen als hilfreich bewertet und erhielt im Schnitt 4.8 Sterne aus 30 Bewertungen. Hast du eine Frage zu Carrier NSA-RH-ROOM oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage

Seite 1/9
RH Room Thermistor
Installation and Operation
#NSA-HH/RH2---CNSA-HH/RH3---C /14/2019 CPR2, CPR211
Specications subject to change without notice.
Catalog No. --- Page of 11808778011 9
Overview
The Carrier Relative Humidity with Thermistor Room Series utilizes a thermoset polymer capacitive
sensing element with a factory tted hydrophobic lter to improve its moisture resistance. The sensing
elements multilayer construction also provides excellent resistance in applications where dust, dirt, oils
and common environmental chemicals are found. The RH room sensors include on board DIP switches
which allow the user to select the desired output signal and can be powered by AC or DC power
sources. Single point field calibration can be performed by using the increment and decrement
calibration DIP switches to adjust your curve up or down in +/- 0.5% increments with each toggle of the
corresponding switches. These enhancements provide increased exibility and outstanding long-term
reliability without the need to replace the sensors in the eld. There are two enclosure options in this
series which should satisfy most commercial decors. Both enclosures feature four-way airow to
minimize self-heating. Three and Five-point NIST Calibration Certificates are available and must be
ordered separately when placing your order.
Applications: Humidication, Dehumidication, Monitoring Indoor Space Humidity, Clean Rooms, Hospitals, Process
Control, Laboratories, Museums, Schools, Oice Buildings, Data Centers, ESD (Anti-Static) Control
Part Numbers
NSA-HH/RH2---C NSA-HH/RH3---C CPR2CPR2
Specications
RH Supply Voltage:
(Reverse Polarity Protected):
4-20 mA: 250 Ohm Load: 15 - 40 VDC / 18 - 28 VAC
500 Ohm Load: 18 - 40 VDC / 18 - 28 VAC
0-5 VDC0-10 VDC: 12 - 40 VDC / 18 - 28 VAC | : 18 - 40 VDC / 18 - 28 VAC
RH Supply Current (VA):
Voltage OutputCurrent Output: 8 mA max (0.32 VA) | : 24 mA max (0.83 VA)
RH Output Load Resistance:
4-20 mA0-5 VDC or 0-10 VDC: 700 Ohms max | : 4K Ohms min
RH Output Signal:
2-wire: 4 - 20 mA (Factory Default)
3-wire: 0-5 or 0-10 VDC & 4 - 20 mA (Field Selectable)
RH Accuracy @ 77°F (25°C ):
+/- 1% over 20% RH Range between 20 to 90% | +/- 2%, 3%, or 5% from 10 to 95%
RH Measurement Range:
0- 100%
Operating RH Range:
0 to 95% RH, non-condensing
Operating Temperature Range:
35 to 122°F (1.5 to 60°C)
Storage Temperature Range:
-40 to 149°F (-40 to 65°C)
RH Stability | Repeatability | Sensitivity:
Less than 2% drift / 5 years | 0.5% RH | 0.1% RH
RH Response Time (T63):
20 Seconds Typical
RH Sensor Type:
Capacitive with Hydrophobic Filter
RH Transmitter Stabilization Time:
30 Minutes (Recommended time before doing accuracy verication) fi
RH Connections | Wire Size:
Screw Terminal Blocks (Polarity Sensitive) | 16 (1.31 mm²) to 26 AWG (0.129 mm²)
RH Terminal Block Torque Rating:
4.43 to 5.31 lb-in (0.5 to 0.6 Nm)
RH NIST Test Points:
Default Test Points: 3 Points (20%, 50% & 80%) or 5 Points (20%, 35%, 50%, 65%
& 80%)
1% NIST Test Points: 5 Points within selected 20% Range (ie. 30%-50% are 30, 35,
40, 45 & 50)
Nominal Thermistor Resistive Output @
77°F (25°C) (Lead Wire Colors) Non-ear Lin
NTC (Negative Temperature Coecient):
10KΩ Nominal
Thermistor Accuracy 32-158°F (0-70°C):
+/- 0.36°F (0.2°C)
Thermistor Power Dissipation Constant:
3 mW/°C
Thermistor Sensor Response Time (T63):
10 Seconds nominal
Temperature Connections | Wire Size:
Screw Terminal Blocks (Polarity Sensitive) | 16 (1.31 mm²) to 26 AWG (0.129 mm²)
Temp Terminal Block Torque Rating:
4.43 to 5.31 lb-in (0.5 to 0.6 Nm)