Eltako DSZ15WD-3x5A Bedienungsanleitung
Eltako Messgeräte DSZ15WD-3x5A
Lies die bedienungsanleitung für Eltako DSZ15WD-3x5A (2 Seiten) kostenlos online; sie gehört zur Kategorie Messgeräte. Dieses Handbuch wurde von 39 Personen als hilfreich bewertet und erhielt im Schnitt 5.0 Sterne aus 20 Bewertungen. Hast du eine Frage zu Eltako DSZ15WD-3x5A oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/2

CT operated energy meter with settable CT ratio and MID.
Maximum current 3x5A. Standby loss 0.5 watt per path only.
Modulair device for DIN-EN 60715 TH35 rail mounting in distribution
cabinets with IP51protection class.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With SO interface as standard.
This three-phase energy meter measures active energy by means of the
current between input and output.
The internal power consumption of 0.5 watt active power per path is neither
metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 5A can be connected.
The inrush current is10mA. The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks
without power supply.
Power consumption is shown by a bar flashing at a rate of10 times per kWh.
On the right next to the display are the keys MODE and SELECT. Press them
to scroll through the menu. First the background lightingswitches on. The
display then shows the total active energy, the active energy of the resettable
memory as well as the instantaneous values of consumption, voltage and
current per phase.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a
bridge over the terminals which are marked with 'JUMPER'. To adjust the CT
ratio to the installed transformer, remove the bridge and reset the energy meter
according to the the display guide, right on this manual. Then block it again
with the bridge. Adjustable current transformer ratios: 5:5, 50:5,100:5,
150:5, 200:5, 250:5, 300:5, 400:5, 500:5, 600:5, 750:5,1000:5,
1250:5 and1500:5.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false'
and the corresponding phase conductor are indicated on the display.
Important !Before working on the current transformers disconnect the voltage
paths of the energy meters.
Three-phase energy meter DSZ15WD-3x5A
with display and MID approval
Only skilled electricians may install this electrical equipment
otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
28 305015 -1
GB
.
Typical connection:
4-wire-connection 3x230/400V
Connect the current transformer terminals on the secondary part to the
phase cunductors which are metered. These connections for the voltage
supply of the energy meters must be secured according to the local
installation regulations.
JUMPER
MODE
SELECT
k
l
K
L
k
l
K
L
k
l
K
L
S0 output
Menu guidance
Produktspezifikationen
| Marke: | Eltako |
| Kategorie: | Messgeräte |
| Modell: | DSZ15WD-3x5A |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Eltako DSZ15WD-3x5A benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Messgeräte Eltako
11 August 2024
21 Juli 2024
15 Juli 2024
12 Juli 2024
Bedienungsanleitung Messgeräte
Neueste Bedienungsanleitung für -Kategorien-
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024