PCE Instruments PCE-WS RS485 Bedienungsanleitung
PCE Instruments
Messgeräte
PCE-WS RS485
Lies die bedienungsanleitung für PCE Instruments PCE-WS RS485 (4 Seiten) kostenlos online; sie gehört zur Kategorie Messgeräte. Dieses Handbuch wurde von 18 Personen als hilfreich bewertet und erhielt im Schnitt 5.0 Sterne aus 9.5 Bewertungen. Hast du eine Frage zu PCE Instruments PCE-WS RS485 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/4


APPLICATIONS
PCE-WS RS485 Modbus has been designed to be used in industrial applications: cranes, solar panels, wind turbines, weather stations,
greenhouses, irrigation systems...
It is usually connected to process displays, PLC’s or dataloggers to display the wind speed and/or set alarms to predened values or to
obtain records during predened periods of time.
OPERATING
Up to 180 km/h of wind speed.
Output is a RS485 MODBUS RTU.
The wind sensor must be xed on a vertical position.
CONNECTION
Unit is provided with a 4x0.65mm cable with 25 meters lenght.
Wire colors:
VCC: blue
GND: white
A: orange
B: yellow
Termination resistor included (120 Ω)
For no termination resistor version, please, contact us.
PROTOCOL
Data format:
1 start bit, 8 data bits and 1 stop bit. 19200 baudios. Even parity. (For other options, please, contact us)
Protocol type:
MODBUS RTU
Addr 04 00 00 00 01 CRCH CRCL
The wind speed in km/h is stored in 2 registers: @30001 y @40001. The user can read this value by using any of the 2 available
functions (Read Input Register and Read Holding Register).
The PCE-WS RS485 default adress is 244 <=> 0xF4. This value is stored in Holding Register @40002 and can be edited by the user.
The user can congure any adress in the range 1 (0x01) to 255 (0xFF).
DIMENSIONS
PCE-WS RS485 Modbus
139
131
91
50
Ø122,73
Ø5,2
10

© PCE Instruments
Example: If Addr =3
READING. METHOD 1
Read request of wind speed from master by (function 0x04):Read Input Register
03 04 00 00 00 01 30 28
Slave's answer (PCE-WS RS485 MODBUS RTU):
03 04 02 SH SL CRCH CRCL
SHSL is the wind speed value in km/h.
Slave's answer example for 100km/h (0x0064):
03 04 02 00 C1 1B64
READING. METHOD 2
Read request of wind speed from master by (función 0x03):Read Holding Register
03 03 00 00 00 01 85 E8
Slave's answer (PCE-WS RS485 MODBUS RTU):
03 03 02 SH SL CRCH CRCL
SHSL is the wind speed value in km/h.
Slave's answer example for 100km/h (0x0064):
03 03 02 00 C064 6F
WRITING
Write request of by Address Write Single Register (función 0x06):
03 00 01 00 NEW_ADDR CRCH CRCL06
Note: The unit adress (Addr) is stored in the Holding Register @40002
Slave's answer (PCE-WS RS485 MODBUS RTU):
03 00 01 00 NEW_ADDR CRCH CRCL06
NEW_ADDR is the new unit address. It must be in the range from 1 (0x01) to 255 (0xFF).
Example for NEW-ADDR 0x02:
Write request:
03 00 01 00 02 58 2906
Slave's answer:
03 00 01 00 02 58 2906
NOTE: the slave's address changes its value inmediately after the answer message.
Produktspezifikationen
Marke: | PCE Instruments |
Kategorie: | Messgeräte |
Modell: | PCE-WS RS485 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit PCE Instruments PCE-WS RS485 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Messgeräte PCE Instruments
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
16 Oktober 2024
Bedienungsanleitung Messgeräte
- Einhell
- IFM
- LaCie
- X-Rite
- Fantini Cosmi
- Soehnle
- Murideo
- Sekonic
- Psiber
- VDO
- Milwaukee
- Omnitronic
- Mitsubishi
- Workzone
- Siig
Neueste Bedienungsanleitung für -Kategorien-
16 Oktober 2024
16 Oktober 2024
15 Oktober 2024
15 Oktober 2024
15 Oktober 2024
15 Oktober 2024
15 Oktober 2024
15 Oktober 2024
15 Oktober 2024
15 Oktober 2024