TH7
Adjusting
Cat. no. CCT15840
Connecting
Installing the probes
Trouble shooting
en
0
515
20
10
+60
+40
+20
0
-20
-40
2
1
3
plage/range
réglage/adjustment
The TH7 thermostat provides temperature control (-40°C to +80°C) when utilised with
heating, hot water and ventilation systems, aquariums, cold stores, etc.
Temperature control is obtained using different types of probe in conjunction with the
activation of a relay output.
b
b
1 Temperature range adjustment.
2 Temperature adjustment within the
desired range.
3 Indicator light: output closed.
Ambient temperature probe cat. no. CCT15846
For all probes:
avoid running connecting cables in close proximity to power cables
use 6/10 type telephone cable (maximum length 70 m) or 1.5 mm
2
shielded copper cable
(maximum length 150 m).
b
v
v
Collar probe cat. no. CCT15848
It should be xed:
to an outgoing hot water pipe
about 1.5 m from the boiler.
b
v
v
Floor temperature probe cat. no. CCT15845
It should be placed:
in a tube set in the oor, between two loops
connections should be brought out to a
distribution box xed to the nearest wall
(for ease of tting or replacement).
b
v
v
External probe cat. no. CCT15847
It must be positioned:
out of direct sunlight, preferably north facing
away from any source of heat (chimney, etc.).
b
v
v
Use adjusting button () to select the range immediately 1
below the temperature required.
Adjust button () to set the exact temperature.2
b
b
Examples:
Temp.requiredRangeAdjustment
80°C+6020
-18°C-202
5°C05
19°C019
Rule: temperature required = range + adjustment.
ProblemPossible causesSolutions
The receiver
is not functioning
bThe thermostat
is not powered
bChecking rst that the TH7 is powered and the
probe correctly wired, set the range to +60 and the
adjustment to 20: output indicator light () should 3
com on
b
Temperature
measurement is
incorrect
bVerify that the probe is connected to terminals ()S
Ensure there is no additional resistance in the
probe wiring, and that no other probe is connected in
parallel with it
b
b
The output
contact is wrongly
connected
bEnsure the output is connected according to your
system’s requirements, either to NO or to NC
b
Characteristics
Supply voltage: 230 V~ ± 10 %
Frequency: 50/60 Hz
Output change-over switch:
16 A/250 V~ cos = 1ϕ
3A/250 V~ cos = 0.6ϕ
Consumption: < 4 VA
Temperature difference (difference in temperature between
switch-on and switch-off): ± 0.2 degrees
Operating temperature: -10°C to +55°C
Storage temperature: -20°C to +60°C
Degree of protection: IP20B as per EN 60529
Connection terminals: 2 x 0.5 to 2.5 mm
2
, rigid and exible
wires
Overall dimensions: 5 modules.
b
b
b
v
v
b
b
b
b
b
b
b
Ambient
temperature
probe
Electronic thermostat
with 6 ranges
723244AE.indd 213/12/2010 12:04:52