Lies die bedienungsanleitung für Schneider WDE002939 (46 Seiten) kostenlos online; sie gehört zur Kategorie Thermostat. Dieses Handbuch wurde von 37 Personen als hilfreich bewertet und erhielt im Schnitt 4.0 Sterne aus 9 Bewertungen. Hast du eine Frage zu Schneider WDE002939 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/46

© 2011 Schneider Electric1
Multi-function application with RTR and FanCoil 1816/1.0
Function overview
This application provides you with the following func-
tions:
•Temperature control with various display options
•Scene function
•Disable function for push-buttons
•Time control
•Valve control
•Push-button functions
All buttons can be assigned different functions inde-
pendently. You can do the following:
•Switch and toggle
•Dim
•Control blinds
•Save and retrieve scenes
•Select a linear regulator function
•Save edge functions
•Adjust setpoints
•Access operation modes and toggle between them
The status LEDs can also be utilised independently of
one another and in a wide variety of ways.
Group addresses
Group addresses are managed dynamically. Maximum
number of group addresses and assignments: 254 ad-
dresses, 255 connections
Notes on this documentation
This application enables you to implement a multitude
of functions with the push-button. However, which func-
tions are possible in each individual case depends on
the KNX devices being controlled (e.g. dimming actua-
tors, switch actuators etc.). The functions described
here therefore show only the settings for this push-but-
ton.
|Many parameters and their settings are depend-
ent on the settings you have already made for oth-
er parameters. This means that some parameters
will appear or disappear and the values available
for selection will change according to settings you
have already made. These dependencies have
not been shown in the table for reasons of clarity.
All settings are always shown.
|Configurable times (staircase timer, ON delay,
OFF delay, cyclic intervals etc.) are set via the
base and factor parameters. The actual time is giv-
en by the multiplication of the two values. Exam-
ple: Base = 1second * factor = 3 gives 3 seconds.
|The bold values in a table are the values set dur-
ing factory configuration.
Before you begin, make a few basic settings in the
"General" tab. You can specify the following:
•Whether the operational LED switches off or displays
that the device is operating.
•How the date and time are received.
•Whether and how the time is sent cyclically to the bus.
•How large the start-up delay for the device should be
after bus voltage recovery.
General settings for date and time
Here you set whether the date and time are received by
two communication objects (3 byte each) or by only one
communication object. In the latter case, there is an 8
byte object available.
If you send the time cyclically to the bus, you either have
an output object with 3 byte or one with 8 byte, depend-
ing on which format you selected.
You can find more details on time control, synchronisa-
tion and master-slave functions in the "Time control"
chapter.
Start-up delay
The start-up delay is the time delay between the bus
voltage recovery and the device's functional start. Set a
time after which the current values can be read by other
KNX devices.
Communication objects
You can select the following communication objects:
Multi-function application with RTR and
FanCoil 1816/1.0
Basic settings
General
ParameterSettings
Switch on operational LEDYes
No
Receive date and timeIn one communication object
In two communication objects
Send time cyclicallyNo
Every minute
Every hour
Daily
Format of sent timeDate/time format (8 byte)
Time format (3 byte)
Device's start-up delay in s (0-255)2-255, 4
FunctionObject nameTypePrioFlagsBehaviour
Time controlDate object input3 byteLowWCReceive
Time controlTime object input3 byteLowWCReceive
Time controlDate/time object
input
8 byteLowWCReceive
Time controlDate/time object
output
8 byteLowCTTransmit
Time controlTime object out-
put
3 byteLowCTTransmit
Produktspezifikationen
| Marke: | Schneider |
| Kategorie: | Thermostat |
| Modell: | WDE002939 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Schneider WDE002939 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Thermostat Schneider
27 September 2024
11 August 2024
4 August 2024
23 Juli 2024
16 Juli 2024
15 Juli 2024
9 November 2022
3 November 2022
Bedienungsanleitung Thermostat
Neueste Bedienungsanleitung für -Kategorien-
27 März 2026
26 März 2026
26 März 2026
26 März 2026
14 März 2026
13 März 2026
12 März 2026
12 März 2026
19 Januar 2026
14 Januar 2026