Lies die bedienungsanleitung für Vemer TDMU (1 Seiten) kostenlos online; sie gehört zur Kategorie Nicht kategorisiert. Dieses Handbuch wurde von 234 Personen als hilfreich bewertet und erhielt im Schnitt 4.9 Sterne aus 117.5 Bewertungen. Hast du eine Frage zu Vemer TDMU oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/1

ISCOM008-0802
Mod. TDMU
User Manual
TDMU MULTIFUNCTION TIME RELAY
Read all instructions carefully
The multifunction time relay
TDMU
is a device standardised in 1-module DIN container,
designed to operate in environments with normal pollution level.
The various alternatives of intervals and functions available made the device easy to adapt in
any type of automatism such as control of light, motors, heating, fun, pumps.
SAFETY WARNINGS
During the installation and operation of the instrument, proceed in accordance with the
instructions below:
1) The instrument should be installed by a competent operator following the
installation diagrams carefully
2) The instrument should be installed in a panel from which no access can be gained to
the terminals after installation
3) Do not power or connect the instrument if any part of it is damaged
4) The electrical system of the building in which the instruments is to be installed
should have a switch and a protective device against over-currents
5) The instrument is designed for installations with over-voltage category III and
pollution level 2, in accordance with the EN 61010-1 standard.
TECHNICAL SPECIFICATIONS
• Power supply: AC/DC 12 ÷ 240V (AC 50/60Hz) -15% ÷ +10%
• Consumption: AC 0,7÷3VA / DC 0,5÷1,7W
• Supply indication: green LED
• Time range with potentiometer: 0,1s ÷ 10 days
• Output
– Number of contacts: 1 changeover
– Output indication: red LED multifunction
– Contact capacity: 16A 250V AC1 / 24V DC
– Inrush current: 30A / < 3 second
– Minimum breaking capacity DC: 500mW
– Breaking capacity: 4000VA / AC1 , 384W / DC
– Mechanical life: 3x107
– Electrical life: 0,7x105
• Operating temperature: -20°C ÷ +55°C
• Storage temperature: -30°C ÷ +70°C
• Protection degree: IP40 from front panel
OPERATION
•
Operation conditions
While installing this device it is necessary to consider temperature rate of ambient devices
so the operation temperature stated in technical parameters is kept. It is necessary to
ensure air circulation so the operation temperature is not exceeded in any case.
It is necessary to avoid placing devices close to sources of electromagnetic disturbances to
ensure their correct function.
It is necessary to pay attention while connecting products to the circuit with appliances
that create electromagnetic disturbances (conductors, motors), or power cables close
to them. It is recommended to have the connection cables of a product (supply and
operating inputs) as short as possible and have them led separately into power conductors.
•
Handling and use
Use a screwdriver with an approximate width 2 mm for installation and setting
Do not use brute force to screw input terminals (maximally 0,5 N/m).
Do not put exceeded pressure on to the holding parts of terminals so the inner
construction of the device is not damaged.
Protect the device against falls and excessive vibrations
Do not overload relay output contacts, mainly while using loads of another category
then AC1
If contacts of relay melted while switching big loads, it is necessary to use an inserted
contactor or power relay rated for required load in the current installation.
For a correct setting of the relay, observe the following operations:
– setting the
Rought time
with its potentiometer (see time ranges in the box
“OPERATING DIAGRAMS”)
– setting the Fine time with its potentiometer (between 10% and 100% of the Rought
time setting)
– setting the Function modes (ten mode available).
REFERENCE STANDARDS
Conformity to the EU directives:
2006/95/EC (Low Voltage)
89/336/EEC modifi ed by 92/31/EEC and 93/68/EEC (EMC)
is declared with reference to the following harmonised standards:
Safety:
EN 61010-1
Electromagnetic compatibility:
EN 61000-6-2, EN 61000-6-4
Dimensions
Wiring diagram
Operating diagrams
1
10
ON
OFF
1
1 10
1
10
10
m
S
h
d
Rough time setting
Fine time setting
(% rough time)
Function setting
Time ranges
0,1-1 s
1-10 s
0,1-1 min
1-10 min
0,1-1 h
1-10 h
0,1-1 day
1-10 days
only ON
only OFF
Delay ON after energization
Delay OFF after energization
Cycler beginning with pause
after energisation
Cycler beginning with impulse
after energisation
Delay OFF after de-energisation,
instant make of output
Delay OFF responding to make of control
contact regardless its length
Delay OFF after break of control
contact with instant output
Delay OFF after make and break of
control contact
Memory (impulse) relay
Pulse generator
Un = 12 ÷ 240V
Produktspezifikationen
Marke: | Vemer |
Kategorie: | Nicht kategorisiert |
Modell: | TDMU |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Vemer TDMU benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Nicht kategorisiert Vemer
5 Juli 2025
2 Oktober 2024
22 September 2024
22 September 2024
18 September 2024
13 September 2024
4 September 2024
2 September 2024
26 August 2024
15 August 2024
Bedienungsanleitung Nicht kategorisiert
- Neets
- Zhiyun
- BeSafe
- Blaze
- BT
- SE Electronics
- Absco
- Black And Decker
- Hooker
- Yorkville
- BikeLogger
- Mega
- Teldat
- King Craft
- Buxton
Neueste Bedienungsanleitung für -Kategorien-
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025