INSTRUCTION MANUAL
DIGITAL CLAMP METER
KEW 2055
1.Features
●
Designedtomeetinternationalsafetystandards.
 
IEC61010-1.IEC61010-031:2002&IEC61010-2-032
 
MeasurementCategory(CAT)IV600V
 
PollutionDegree2
●
Double molded main body provides comfortable
singlehandedgrip
 
●
DataHoldFunction
●
LCD Backlight function to facilitate working at
dimlylitsituations.
●
RELfunctiontoindicatemeasurementvariation.
 
(Current,voltage,Resistancemeasurement)
●
MIN/MAX functionenables easyreading ofmin &
maxvalueduringmeasurement.
●
WithContinuity&DiodeCheckFunction
●
NCV
(
Non Contact Voltage
)
Function for wiring
check.
●
600Vinputprotection.
●
Sleepfunctiontoextendbatterylife.
●
WithBarGraph,6039counts
2. Safety Warnings
This instrument has been designed, manufactured and
testedaccordingtoIEC61010:Safetyrequirementsfor
Electronic Measuring apparatus, anddelivered in
the best condition after passed the inspection. This
instructionmanual contains warningsand safety
rules which must be observedby the user to ensure
safeoperation of the instrument and retain it in safe
condition.
Therefore, readthrough theseoperating instructions
beforeusingtheinstrument.
 
WARNING
●
Read throughand understandthe instructions
contained inthis manual before usingthe
instrument.
●
Keepthemanual at handto enable quick
referencewhenevernecessary.
●
Theinstrumentistobeusedonlyinitsintended
applications.
●
U n d e r s t a n da n df o l l owa l lt h es a f e t y
instructionscontainedinthemanual.
Failure tofollow the instructions may cause injury,
instrument damage and/or damage toequipment
undertest. Kyoritsu isby no meansliable for
any damage resultingfrom the instrument in
contradictiontothiscautionarynote.
Thesymbol indicatedontheinstrumentmeansthat
theusermustrefertotherelatedpartsinthemanual
forsafe operation ofthe instrument. It isessential to
readthe instructions whereverthesymbol appears
inthemanual.

DANGER is reserved for conditions and actions
that are likely to cause serious or fatal injury.

WARNING is reserved for conditions and actions
that can cause serious or fatal injury.

CAUTION is reserved for conditions and actions
that can cause injury or instrument damage.
●
Marks listed in the table below are usedon this
instrument.
Usermustrefertothemanual.
Instrumentwithdoubleorreinforcedinsulation
Indicates that this instrument can clampon
bareconductorswhenmeasuring avoltage
corresponding to the applicablemeasurement
category,whichismarkednexttothissymbol.
AC
 DC
AC&DC
Thisinstrumentsatisfiesthemarkingrequirement
defined inthe WEEE Directive (2002/96/EC).
This symbol indicates separate collection for
electricalandelectronicequipment.
 
DANGER
●
Never make measurement on a circuit in which
voltageoverAC600Vexists.
●
Donot attempt to makemeasurementin the
presenceof flammable gasses. Otherwise, the use
of the instrument may cause sparking, whichcan
leadtoanexplosion.
●
Transformerjawtips aredesignednot toshort
the circuit under test. If equipment under test
hasexposed conductive parts,however, extra
precaution shouldbe takento minimize the
possibilityofshorting.
●
Neverattempttousetheinstrumentifitssurface
oryourhandiswet.
●
Donot exceed the maximumallowable input of
anymeasuringrange.
●
N e ve rop e nt h eB a t t e ry c ov e rd u ri n ga
measurement.
●
The instrument is to beused only in its intended
applications orconditions.Otherwise, safety
functionsequippedwiththeinstrumentdoesn
twork,
and instrumentdamageorseriouspersonalinjury
maybecaused.
●
Verify proper operation ona known source before
use ortaking actionas a result indicationof the
instrument.
●
Keepyourfingersandhandsbehindtheprotective
fingerguardduringmeasurement.
 
WARNING
●
Never attempt to make measurement if any
abnormal conditions, such as broken case and
exposedmetalpartsarefoundontheinstrument.
 
●
Do notrotate the FunctionSwitch while the test
leadsarebeingconnected.
●
Do not install substitute parts or make any
modification totheinstrument. Forrepair or
re-calibration, returnthe instrumentto yourlocal
distributorfromwhereitwaspurchased.
●
Donot try to replace the batteries if the surface
oftheinstrumentiswet.
●
Disconnect all thecordsandcables from the
object under test and poweroffthe instrument
before openingtheBattery Coverfor Battery
replacement.
●
Verify proper operation ona known source before
useortakingactionasaresultoftheindicationof
theinstrument.
●
Use appropriate personal protective equipment
such asinsulating gloves, Insulating boots, and
safetyglasses.
●
Stop using the test lead if the outer jacketis
damaged and the inner metal orcolor jacket is
exposed.
 
CAUTION
●
SettheFunctionSwitchtoanappropriateposition
beforestartingmeasurement.
 
●
Firmlyinsertthetestleads.
 
●
Disconnectthetestleadsfromtheinstrumentfor
currentmeasurement.
 
●
Do not exposethe instrument to the directsun,
hightemperatureandhumidityordewfall.
 
●
Altitude 2000m or less. Appropriate operating
temperatureiswithin0
℃
and40
℃
.
●
This instrument isn
t dust & water proofed. Keep
awayfromdustandwater.
●
Be sure to power off theinstrument after use.
Whentheinstrumentwill notbein usefora long
period,placeit in storage after removing the
batteries.
●
Use a cloth dipped in water or neutraldetergent
for cleaning the instrument. Do not use abrasives
orsolvents.
Measurement Category
To ensuresafe operationof measuring instruments,
IEC 61010establishes safety standardsfor various
electrical environments,categorized as Oto CATIV,
and calledmeasurement categories.Higher-numbered
categories correspondto electrical environments with
greatermomentary energy,so a measuringinstrument
designedforCAT III environmentscanendure greater
momentaryenergythanonedesignedforCATII.
O
:Circuits whichare notdirectly connected
tothemainspowersupply.
CAT II
:Electrical circuits of equipmentconnected
toanACelectricaloutletbyapowercord.
CAT III
:Primary electrical circuits of the
equipment connected directly to the
distribution panel,and feeders fromthe
distributionpaneltooutlets.
CAT IV
:Thecircuit from theservice dropto the
service entrance,and to the power meter
andprimaryover-currentprotectiondevice
(distributionpanel).
3. Specification
3-1. Measuring range & accuracy
(accuracyguaranteedat23
℃ ±
5
℃
.humidity45
〜
85%)
ACCurrent600A,1000AFunction
Function Measuring
Range Accuracy
600A 0-600.0A
±
1.5%rdg
±
5dgt
(50/60Hz)
±
3.5%rdg
±
8dgt
(40-400Hz)
1000A 0-1000A
DCCurrent600A,1000AFunction
Function Measuring
Range Accuracy
600A
0-600.0A
±
1.5%rdg
±
5dgt
1000A
0-1000A
ACVoltageFunction

(
Auto-ranging,Inputimpedance:approx.10M
Ω)
Range Measuring
Range Accuracy
6/60/600V 1-600.0V
±
1.3%rdg
±
4dgt(50/60Hz)
±
3.0%rdg
±
5dgt(40
〜
400Hz)
DCVoltageFunction

(
Auto-ranging,Inputimpedance:approx.10M
Ω)
Range Measuring
Range Accuracy
600mV/6/
60/600V 0-600.0V
±
1.0%rdg
±
3dgt
Resistance
(
Continuity/DiodeCheck
)
Function
Range Measuring
Range Accuracy
600
Ω
/6k/
60k/600k
Ω
6M
Ω
0-6M
Ω ±
1.0%rdg
±
5dgt
60M
Ω
6.00M-
60.00M
Ω±
5%rdg
±
8dgt
ContBuzzer 0-600.0
Ω
Thresholdvalue:60
Ω±
30
Ω
Diode Testvoltage:0-2V
Frequency/ DUTYFunction
(
Auto-ranging for
Frequency
)
Range Measuring
Range Accuracy
ACA 40Hz
−
400Hz
±
0.5%rdg
±
5dgt
ACV 1Hz
〜
10kHz
0.1-99.9%
(Pulsewidth/Pulseperiod)
±
2.5%rdg
±
5dgt
Note:Measurableinputsare:40Vrms@ACVor
60Arms@AC600A,350A@AC1000ARange
3-2. General Specification
●
Modeofoperation
 
:
Δ
∑mode
●
Display 
 
:max.6039counts

(Frequency:9999)&Bargraph
●
Over-range indication:"OL" displayed when exceeding
the measuring range. (except for AC/DCV and 1000A
Function)
●
Rangeswitching :
 
Auto-ranging/Voltage,ResistanceRange
 
Singlerange/Continuity,Diodecheckand
DUTY
●
Samplerate
:threetimespersecond
●
Functionalconstruction:
 
OFF/ACA/DCA/ACV/DCV/
Ω
●
Keys :
 
SELECT(AC/DCswitching&/
Ω
/ /),REL
Δ
,
 
Hz/DUTY,MIN/MAX,HOLD/BackLight
●
Powersource :DC3V/R03(UM-4)x2pcs
●
Lowbatterywarning
:
" "markisdisplayedat
 
2.4V
±
0.15Vorless.
●
Temperature & humidity: 23
℃ ±
5
℃
,relative humidity
accuracyguaranteed85%orless(nocondensation)
●
Operatingtemperature:0
〜
40
℃
,relativehumidity
 
&humidityrange85%orless(nocondensation)
●
Storagetemperature :-20
〜
60
℃
,relativehumidity
 
&humidityrange85%orless(nocondensation)
●
Currentconsumption:approx.12mA
●
SleepFunction:Automaticallypoweredoffinabout
 
15minafterthelastFunctionswitchoperation.
 
Pressany key or rotate the Function Switch from
OFFtoanypositiontoexitfromtheSleepstate.
●
Locationforuse
Outdooruse,Altitudeupto2000m
●
ApplicableStandards
 
IEC61010-1,61010-2-032,61010-2-033
 
MeasurementCATIV600VPollutiondegree2
 
IEC61010-031
 
EMC
:
EN61326-1
 ・
EN55022
 ・
EN61000-4-2(performancecriterionB)
 ・
EN61000-4-3(performancecriterionB)
●
RoHS
:
EN50581
●
OverloadProtection
 
CurrentRange :1200AAC/DC/10sec
 
VoltageRange :720VAC/DC/10sec
 
ResistanceRange :600VAC/DC/10sec
●
WithstandVoltage
 
6720VAC
(
TRMS50/60Hz
)
/5sec
 
(betweenJawsandelectricalcircuit/betweeninternal
 
circuitandenclosure)
●
InsulationResistance:10M
Ω
ormore/1000V
 (
betweenelectricalcircuitandenclosure
)
●
Conductorsize
 
approx.40mm
●
Dimension
 
approx.254(L)
×
82(W)
×
36(D)mm
●
Weight:approx.:310g
●
Accessories
 
 
TestLeads Model7066A/1set
 
BatteryR03
(
UM-4
)
/2pcs
 
InstructionmanualEnglish,Japanese/1pce
 
CarriyngCaseModel9094/1pcs
3-3. Function Keys
The"
●
"markshowsavailablefunctionateachRange.
DCCurrentMeasurement
HOLD SELECTZEROHz/
DUTY MAX/
MIN
ACA
●●●●●
ACV
●
-
●●●
DCA
●●●
-
●
DCV
●
-
●
-
●
Ω●●●
-
●
-
●
---
-
●
---
4. Preparation for measurement
4-1. Checking Battery Voltage
Set theFunctionSwitch toanyposition otherthan
"
OFF
".When thedisplayis clearwithout  "
BATT
" mark,
showing, batteryvoltage is enough. When the display
is blankor
 
 "
BATT
" mark isindicated,replacethe
batteriesaccordingtoSection7,BatteryReplacement.
 
CAUTION
The Sleepfeature automaticallypowers the
instrumentoffinabout 15minafterthe lastswitch
or key operation. Therefore, the display may be
blankevenwiththeFunctionSwitchsettoaposition
other than "
OFF
". Tooperate theinstrument in this
case, turn the switch back to the  "
OFF
"  position,
thentoanyotherposition,orpressanykey.Replace
the batteriesifnothingwasdisplayed afterabove
operations.
4-2. Checking Switch Setting & Operation
Confirm the Function Switch is set to the correct
position,the instrument isset to thecorrect
measurementmode,
and the Datahold function is disabled. Otherwise,
desiredmeasurementcannotbemade.
5. Measurement
5-1. AC Current Measurement
 
DANGER
●
Nevermake measurement on a circuit in which
voltage over AC600V exists to avoid getting
electricalshock.
●
Transformer jaw tips are designed not to short
the circuit under test. Ifequipment under testhas
exposedconductiveparts,however,extraprecaution
shouldbe taken to minimize the possibility of
shorting.
●
Do not make measurement with the Battery Cover
removed.
●
Disconnect the test leadsfrom the instrument for
currentmeasurement.
●
Keep yourfingersand handsbehindthe barrieron
theinstrumentduringameasurement.
(1)Set theFunction Switchto "
600A
" or"
1000A
"
position.
AChasbeenselectedbydefault;presstheSELECT
key, whenDC hasbeenselected, tochangeit to
AC.AC mark isdisplayed at theupper left onthe
display.
(2)Pressthetriggertoopenthetransformerjawsand
clampthemontotheoneconductorundertest,then
take thereading on the display. Pressing the "
Hz/
DUTY
" Key switches the indication in following
sequence.
AC Current
⇨
Hz
⇨
DUTY
Hz/DUTY
 Function requires 60A ormore at AC600A
Rangeand350AormoreatAC1000Arange.
 
CAUTION
●
Max conductorsize for KEW2055 isapprox
dia. 40mm. Duringcurrent measurement, keep
the trans former jaws fully closed.Other wise,
accuratemeasurementscannotbetaken.
5-2. DC Current Measurement
 
DANGER
●
Never make measurementon a circuitin which
voltage overDC600Vexists toavoid getting
electricalshock.
●
DonotmakemeasurementwiththeBatteryCover
removed.
●
Keepyourfingersandhandsbehindthebarrieron
theinstrumentduringameasurement.
(1)Set theFunction Switchto "
600A
" or"
1000A
"
position. AC has been selected by default; press
the SELECT key, when AC has been selected, to
changeittoDC.
DC mark isdisplayed atthe upperleft on the
display.
Barrier
O: Device which is
not directly
connected to the
mains power supply
Protectivefingerguard(Barrier)
:
Itisapartprovidingprotection againstelectrical
shock and ensuring theminimum required airand
creepagedistances.
Cap
:
UncappedconditionforCATIIenvironment
CappedconditionforCATIII/IVenvironments
TheCapshuldbefirmlyattachedtotheprobes.
Whenthe instrument and the testlead are combined
andusedtogether,whicheverlowercategoryeitherof
thembelongstowillbeapplied.