BOSCH HMB
Installation Instructions
OVERVIEW - Engineer’s Specification
The BOSCH HMB system shall include one Master Panel and one or more Distributed
Panels. The system shall be microprocessor based, and shall be compatible for use with
contact closures from the Fire Alarm Control Panel, (FACP). The system shall have a high-
speed communication bus and have the capacity for 6 channels of combined audio and data
on a single pair of wires. The field wiring for the communication bus may be configured for
either Style 4 or Style 7 supervision. The system shall have the capacity for Fire Fighters
Phone communication. The system shall have a minimum capacity of 2048 monitor and
control points.
The Master Panel shall contain an integral microphone, dual channel digital message
repeater, (DMR) and digital tone generator, 120 VAC power supply, and battery charger. The
system shall be modular in design, and shall be expandable such that additional system
control points may be configured. The system shall include integral self-diagnostic routines
that shall continually monitor system status, and shall indicate the precise type of trouble
conditions should they occur in the system. A trouble condition within the system shall cause
a trouble indication to be transmitted to the FACP.
Distributed panels shall provide a minimum of 4 Class "B" (Style Y) speaker circuits,
expandable to eight total. Alternately, panel may be configured for 4 Class "A" (Style Z)
speaker circuits. Panel will provide up to 6 simultaneous audio channels, up to 16 Fire
Phone circuits. Amplifiers will contain their own power supplies, battery chargers and provide
auxiliary power for other components. Speaker circuits shall be supervised for short and open
circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.
System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of
an alarm signal and evacuation message to the appropriate area. Non-Alarm areas may
receive alert tones and messages as required or activated by the FACP.
The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.
To prevent unauthorized tampering, the voice evacuation system shall disable the
microphone if the microphone is keyed continuously for 3 minutes or more. Systems that do
not have this feature shall not be acceptable.
P/N B-5010 REV. C
130 Perinton Parkway, Fairport, NY 11450
Customer Service: (800) 289-0096
Technical Support: (888) 886-6189
Produktspezifikationen
| Marke: | Bosch |
| Kategorie: | Detektor |
| Modell: | MB-MBR |
| Menge pro Packung: | 1 Stück(e) |
| Eingangsspannung: | 24 V |
| Markenkompatibilität: | Bosch |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Bosch MB-MBR benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Detektor Bosch
Bosch PDO 6 Bedienungsanleitung Bosch MB-PWR Bedienungsanleitung Bosch Truvo Bedienungsanleitung Bosch F220-B6C Bedienungsanleitung Bosch GMS 100-23 Professional Bedienungsanleitung
Alle Bosch Detektor Bedienungsanleitungen
Bedienungsanleitung Detektor
Neueste Bedienungsanleitungen für Detektor
PATLITE SZP-102 Bedienungsanleitung Megger VF3 Bedienungsanleitung Seaward AGL-5 Bedienungsanleitung Megger VF6 EX Bedienungsanleitung Megger MCT105 Bedienungsanleitung XP Pinpointer MI-4 Bedienungsanleitung STI -9729 Bedienungsanleitung Voxx CAMSBAR Bedienungsanleitung Uniden GRAN ALCANCE R3 Bedienungsanleitung Schabus WWD 150 Bedienungsanleitung