Lies die bedienungsanleitung für IFM DI6005 (7 Seiten) kostenlos online; sie gehört zur Kategorie Nicht kategorisiert. Dieses Handbuch wurde von 11 Personen als hilfreich bewertet und erhielt im Schnitt 4.4 Sterne aus 6 Bewertungen. Hast du eine Frage zu IFM DI6005 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/7

Operating instructions
Compact speed monitor M18
DI6005
11473498 / 0007 / 2022
GB

DI6005 Compact speed monitor M18
6
4 Function
The unit has two independently configurable switching channels.
About the measuring function:
The sensor measures the time between 2 successive transitions from “undamped” to “damped”. The
pulse/pause ratio undamped/damped is not relevant, but both the damped and undamped states
should be reliably detected.
If the frequency determined from this time [1/min] is below the last measured value, the output speed
decreases with 1/t. At less than 0.5 pulses/min, 0.0 pulses/min is measured. There is no underload.
An overload is present at over 32,000.0 pulses/min (533 Hz).
4.1 Single-point mode
SP1
H
SSC
0 PDV
OFF ON
Fig.1: Normally open = low active (factory setting)
SP1: Switch-off point
SP1+H: Switch-on point
If a set rotational speed is not reached, the transistor output will signal this as non-conducting.
H
SSC
0 PDV
SP1
ON OFF
Fig.2: Normally closed = high active
SP1: Switch-on point
SP1+H: Switch-off point
If a set rotational speed is not reached, the transistor output will signal this as conducting.
Imp./min.
3000
2500
2000
1500
1000
500
0
1
0
1
0
OUT
2
3
4
1
OUT
SP1 + H
SP1
t
1: Power-on delay time
2: Start-up delay
3: Normally open = low active
4: Normally closed = high active

DI6005 Compact speed monitor M18
8
4.3 Two-point mode
SP2 SP1
H
SSC
0 PDV
OFF ON
Fig.5: Normally open = low active
SP2: Switch-off point
SP1: Switch-on point
If a set rotational speed is not reached, the transistor output will signal this as non-conducting.
H
SSC
0 PDV
SP2 SP1
ON OFF
Fig.6: Normally closed = high active
SP2: Switch-on point
SP1: Switch-off point
If a set rotational speed is not reached, the transistor output will signal this as conducting.
Imp./min.
3000
2500
2000
1500
1000
500
0
1
0
1
0
OUT
2
3
4
1
OUT
SP1
SP2
t
1: Power-on delay time
2: Start-up delay
3: Normally open = low active
4: Normally closed = high active
It is also possible to configure SP1 as the lower switch point and SP2 as the upper switch point.
The lower switch point must be at least 10% lower than the higher switch point.
4.4 IO-Link mode
IO-Link allows the configuration of internal parameters such as switching threshold, start-up delay and
switching behaviour (normally closed/normally open) as well as reading the current measured values.
Furthermore IO-Link protects against signal faults and measured value losses as well as tampering
with the sensor. IO-Link facilitates the identification of connected devices in the system and provides
diagnostic functions.
Produktspezifikationen
Marke: | IFM |
Kategorie: | Nicht kategorisiert |
Modell: | DI6005 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit IFM DI6005 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Nicht kategorisiert IFM
25 Juli 2025
25 Juli 2025
25 Juli 2025
25 Juli 2025
21 Juli 2025
20 Juli 2025
20 Juli 2025
20 Juli 2025
20 Juli 2025
20 Juli 2025
Bedienungsanleitung Nicht kategorisiert
- ORNO
- Nils Fun
- Helios Preisser
- Britax-Römer
- Telefunken
- Arebos
- Magliner
- GoldenEar Technology
- Kerbl
- Dresden Elektronik
- Briggs & Stratton
- Honda
- Kreg
- Pfister
- TOA
Neueste Bedienungsanleitung für -Kategorien-
30 Juli 2025
30 Juli 2025
30 Juli 2025
30 Juli 2025
30 Juli 2025
30 Juli 2025
30 Juli 2025
30 Juli 2025
30 Juli 2025
30 Juli 2025