Zurn Z1186 Bedienungsanleitung
Zurn Nicht kategorisiert Z1186
Lies die bedienungsanleitung für Zurn Z1186 (4 Seiten) kostenlos online; sie gehört zur Kategorie Nicht kategorisiert. Dieses Handbuch wurde von 38 Personen als hilfreich bewertet und erhielt im Schnitt 4.7 Sterne aus 19.5 Bewertungen. Hast du eine Frage zu Zurn Z1186 oder möchtest du andere Nutzer dieses Produkts befragen? Stelle eine Frage
Seite 1/4

Z1186 AND Z1188 OIL INTERCEPTORS
Zurn Industries, LLCSpecification Drainage Operation|
1801 Pittsburgh Avenue, Erie, PA U.S.A. 16502 · Ph. 855-663-9876, Fax 814-454-7929
In Canada |Zurn Industries Limited
3544 Nashua Drive, Mississauga, Ontario L4V 1L2 · Ph. 905-405-8272, Fax 905-405-1292
www.zurn.com
Rev.D
Date:04/10/2018
C.N. No.139851
Form No.IT84
Page 1 of 4
®
Dimensional Data (inches and [ mm ]) are Subject to Manufacturing Tolerances and Change Without Notice
PURPOSE
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
ADVERTENCIA: Cáncer y daño reproductivo - www.P65Warnings.ca.gov
AVERTISSEMENT: Cancer et effets néfastes sur la reproduction - www.P65Warnings.ca.gov
For nearly fifty years, Zurn oil interceptors have been used in plumbing waste systems to help protect property and the environ-
ment against explosion, fire, and pollution. Zurn oil interceptors are designed similar to the grease interceptors. Both work on the
principle that oils are lighter than water and thus gravity causes the oil to rise to the surface of the water. Zurn oil interceptors come
equipped with a removable combination pressure equalizing/flow diffusing baffle and sediment bucket on the inlet to trap stones, grit,
and other substances. Their solid flow-diffusing baffle eliminates turbulence and allows for high efficiency of separation.
All Zurn Z1186 and Z1188 oil interceptors are supplied with an adjustable oil draw-off assembly and vent connection. The inter-
ceptors are constructed of 100% steel, coated with a blue acid resistant epoxy. All Zurn oil interceptors are listed by IAPMO. If you
require an oil interceptor not listed call 814/455-0921, or fax 814/871-6141 your requirements to the Zurn Engineering Department
for assistance.
HOW THE ZURN OIL INTERCEPTOR OPERATES
The solid baffle plate opposite the inlet to the oil interceptor diffuses the flow into the interceptor and lessens the
turbulence of the oil-laden water as it enters the intercepting chamber. Solids and sludge carried in the water are stopped by the
baffle and collected in the solids retaining bucket between the inlet and the flow-retarding baffle. Such accumulation can then be
removed. The resulting quiet, even flow of water through the interceptor permits the oils and other light density substances to rise to
the surface by the “flotation” principle of separation. Maximum separation and interception is affected in proportion to the elimination of
turbulence of wastewater within the interceptor. The unique Zurn baffle/bucket design permits almost 90 percent of the interior of the
interceptor to be used for the function of oil separation.
INSTALLATION CONSIDERATIONS
Install interceptor in the building sewer line. The interceptor may be set on the floor, partially recessed in the floor, top flush with
the floor, or fully recessed below the floor to suit piping and structural conditions.
Anticipate sufficient clearance for removal of interceptor cover for cleaning. Also, take into consideration the placement of flow con-
trol fitting, vent requirements, and draw-off piping.
Recommended Installations
Commercial UsesIndustrial Uses
Filling and Service StationsMachine Shops
Maintenance GaragesRefineries
Airport HangarsFabrication and Welding Plants
Laundries and Cleaning EstablishmentsFoundries
Parking Facilities
SIZING
The gallons-per-minute rate of flow through the drainage line into the interceptor is the main consideration in selecting the proper
size oil interceptor. In addition, the viscosity characteristics and probable amounts of oils and other light density substances to be
separated should be taken into consideration since the volume involved may influence the intercepting chamber size. The larger
the interceptor, the higher the flow rate it will handle efficiently and the larger quantity of oil it will separate. If the oil interceptor is
too small, an overload condition will develop and some of the oil will be carried through the oil interceptor in the wastewater and pass
into the drainage system. Overload conditions may also cause water levels in the trap to rise, thus water will be drawn off through
the oil draw off.
VENTING
All Zurn oil interceptors are furnished with 2” IPS vent and drawoff connections on both the right and left hand sides of the inter-
ceptor with plugs in one side. If necessary, the vent and drawoff connections can be changed from one side to the other at the
time of installation, by switching the plugs.
The vent connections are located above the adjustable gravity oil draw-off standpipe in the intercepting chamber. Thus, the volatile
gases rising from the intercepted substances are carried from the interceptor to the atmosphere.
Produktspezifikationen
| Marke: | Zurn |
| Kategorie: | Nicht kategorisiert |
| Modell: | Z1186 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Zurn Z1186 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Nicht kategorisiert Zurn
8 Dezember 2025
7 Dezember 2025
6 Dezember 2025
5 Dezember 2025
5 Dezember 2025
4 Dezember 2025
4 Dezember 2025
3 Dezember 2025
3 Dezember 2025
14 Juli 2025
Bedienungsanleitung Nicht kategorisiert
Neueste Bedienungsanleitung für -Kategorien-
22 Januar 2026
22 Januar 2026
22 Januar 2026
22 Januar 2026
22 Januar 2026
22 Januar 2026
22 Januar 2026
22 Januar 2026
22 Januar 2026
22 Januar 2026